Rockwell Automation Current Input Module User Manual
Page 40
4Ć22
Register 3005 = Register contains the current input channel's High
High alarm value. This value is provided by the
data table in the 5000Ćseries registers.
Register 3006 = Register contains the current input channel's High
alarm value. This value is provided by the data
table in the 5000Ćseries registers.
Register 3007 = Register contains the current input channel's Low
alarm value. This value is provided by the data
table in the 5000Ćseries registers.
Register 3010 = Register contains the current input channel's Low
Low alarm value. This value is provided by the
data table in the 5000Ćseries registers.
Register 3011 = Register contains the current input channel's
configuration command. This value is provided by
the data table in the 5000Ćseries registers.
Registers 3100 to 3137Ă=Registers contain the data read from the
Current Input module.
Registers 5000 to 5027Ă=Registers contain the data used to
configureĂthe current input channels. Each
channelĂuses eight registers:
Max.
Scale
Min.
Scale
Average
Samples
High
High
High
Low
Low
Low
Config.
Command
Reg. 5000ă=Ăă2000
Reg. 5010ă=Ăă3000
Reg. 5020ă=Ă10000
-100
0
0
20
20
20
1800
2500
9000
1600
2000
7500
ă400
ă500
2500
ăă0
ă250
1000
12288*
12288ă
12288ă
*12288 = 3000 Hex
Note that you must use the POINTMONITOR function to enter these
values into the 5000Ćseries registers before you begin executing the
program.
Register 5200 = Register contains the value (0) for the READY
command.