! This task configures three channels:
40
!
Channel 0 monitors the level of a liquid in a tank
45
!
Channel 1 monitors the startup pressure of a process
50
!
Channel 2 monitors the operating pressure of a process
55
!
If any configuration fails, SHUTDOWN@ is set
60
!
65
! This task checks for alarms once per second.
70
!
If any channel has an out of range status condition,
&
!
SHUTDOWN@ is set
75
!
If any channel has a high or low alarm, WARNING@ is set
80
!
If any channel has a highĆhigh or lowĆlow alarm,
&
!
SHUTDOWN@ is set
90
!
100
! ********************* LOCAL VARIABLES *******************
110
!
120
LOCAL CHANNEL%
130
!
200
! ********************* COMMON VARIABLES ******************
210
!
220
COMMON TANK_LEVEL%
\! Tank level read by the CIM card
230
COMMON START_PROCESS%
\! Pressure read by the CIM card
&
\! during the startup process
240
COMMON OP_PROCESS%
\! Pressure read by the CIM card
&
\! during the operation process
245
!
300
COMMON TANK_HH_ALARM@
\! Tank highĆhigh alarm status
310
COMMON TANK_H_ALARM@
\! Tank high alarm status
320
COMMON TANK_L_ALARM@
\! Tank low alarm status
330
COMMON TANK_LL_ALARM@
\! Tank lowĆlow alarm status
340
!
400
COMMON START_HH_ALARM@
\! HighĆhigh alarm status during the
&
\! startup process
410
COMMON START_H_ALARM@
\! High alarm status during the
&
\! startup process
420
COMMON START_L_ALARM@
\! Low alarm status during the
&
\! startup process
430
COMMON START_LL_ALARM@
\! LowĆlow alarm status during the
&
\! startup process
440
!
500
COMMON OP_HH_ALARM@
\! HighĆhigh alarm status during
&
\! the operation process
510
COMMON OP_H_ALARM@
\! High alarm status during the
&
\! operation process
520
COMMON OP_L_ALARM@
\! Low alarm status during the
&
\! operation process
530
COMMON OP_LL_ALARM@
\! LowĆlow alarm status during the
&
\! operation process
540
!
600
COMMON CNF_CHAN_NUM%
\! Channel number (Register 23)
610
COMMON CNF_MAX%
\! Maximum scaling value (Register 24)
620
COMMON CNF_MIN%
\! Minimum scaling value (Register 25)
630
COMMON CNF_AVE_SAMPLE%
\! Number of running average samples (Register 26)
640
COMMON CNF_HH_ALARM%
\! HighĆhigh alarm value (Register 27)
650
COMMON CNF_H_ALARM%
\! High alarm value (Register 28)
660
COMMON CNF_L_ALARM%
\! Low alarm value (Register 29)
670
COMMON CNF_LL_ALARM%
\! LowĆlow alarm value (Register 30)
680
COMMON CNF_COMMAND%
\! Configuration command (Register 31)
690
COMMON CNF_COMP@
\! Configuration complete (Register 22, bit 15)
700
COMMON CNF_ERROR@
\! True if configuration error occurs (Register 22, bit 14)
710
COMMON WARNING@
\! True if any channel has a high or
&
\! low alarm
720
COMMON SHUTDOWN@
\! True if any channel has a lowĆlow
&
\! or highĆhigh alarm or an outĆofĆ
&
\! range or configuration error
730
COMMON OUT_OF_RANGE%
\! NonĆzero if any channel output
&
\! value is out of range
Figure 4.12 Ć Sample DCS 5000/AutoMax Current Input Application Task