Electrostatic charge, Outputs, Mount the 1797-ps2e2 power supply – Rockwell Automation 1797-PS2E2 FLEX Ex Power Supply User Manual
Page 8
![background image](/manuals/580493/8/background.png)
8 FLEX Ex Power Supply
Publication
1797-5.8 - June 2010
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near this module.
WARNING Avoid electrostatic charging.
ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA
ELETROSTÁTICA.
For your convenience, a sign that can be cut out and posted is included on the
last page of these installation instructions.
Outputs
When using an intrinsically-safe electrical apparatus according to EN
60079-11, the European directives and regulations must be followed.
The channels in the power supply are electrically connected to each other and
have a common +V line.
Mount the 1797-PS2E2 Power Supply
Follow these directions to properly install the 1797-PS2E2 power supply.
Refer to the Installation and Commissioning section, page 7, for important
precautions and considerations.
1. Remove the screws on the cover of the power supply Ex e terminal
box to access the input and output terminals.
2. Thread the blue IS-safe output power wiring through the blue IS
compression seals.
IMPORTANT
You cannot interconnect lines because of the intrinsic safety
requirements.
ATTENTION
Use star washers and nuts to make sure you have a good electrical
connection. Scrape the paint off the back panel in those areas where
grounding bolts will be located.