beautypg.com

Rockwell Automation 1798-PFTP1 FlexArmor PROFIBUS Field Termination Plug User Manual

Page 7

background image

FlexArmor PROFIBUS Field Termination Plug 7

Publication 1798-IN005B-EN-P - April 2002

1798-PFTP1 Specifications (continued)

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
–20 to 60°C (–4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–40 to 85°C (–40 to 185°F)

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on power ports
±1kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power
ports
+1kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz