Output map, Repair, Output map repair – Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual
Page 14: 14 flex ex frequency input module publication
14 FLEX Ex Frequency Input Module
Publication
1797-5.9 - June 2010
Output Map
Repair
This module is not field-repairable. Any attempt to open this module will void
the warranty and IS certification. If repair is necessary, return this module to
the factory.
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word
Write
0
Out
Enb
FSM
FR
Ch
0
Number of
Pulses to
terminate
sampling Ch 0
MPM
Ch 0
Alt
Pulse
Term
LF
FR
Ch
1
Number of
Pulses to
terminate
sampling Ch 1
MPM
Ch 1
1
Maximum Frequency 0…32,767 or 0.0…3,276.7 or
Absolute Value of Acceleration 0…32,767 - Channel 0
2
Frequency Scaling Divisor 1…255 Ch 0
Frequency Scaling Multiplier 1…255 Ch 0
3
WO
FG
Ch
0
WO
FF
Ch 0
IGI
Ch
0
IFI
Ch
0
Minimum
Frequency Sample
Time
Ch 0
Init
St Up
Ch 0
ACT
0…3
Ch 0
F/A
AS
Ch 0
MPDM
Ch 0
WOFM
Ch 0
4
Maximum Frequency 0…32,767 or 0.0…3,276.7 or
Absolute Value of Acceleration 0…32767 - Channel 1
5
Frequency Scaling Divisor 1…255 Ch 1
Frequency Scaling Multiplier 1…255 Ch 1
6
WO
FG
Ch
1
WO
FF
Ch 1
IGI
Ch
1
IFI
Ch
1
Minimum
Frequency Sample
Time
Ch 1
Init
St Up
Ch 1
ACT
0…3
Ch 1
F/A
AS
Ch 1
MPDM
Ch 1
WOFM
Ch 1
7
Reserved
Where:
Out Enb = Output enable
FSM = Fault state mode
FR = Frequency range
MPM = Missing pulse multiplier
LF = Local fault mode
F/AAS = Frequency/Accel alarm select
WOOF = Wire-off fault frequency
WOFG = Wire-off fault gate
WOFM = Wire-off fault mode
IGI = Invert gate input
FI = Invert frequency input
ACT = Acceleration calculation time
MPDM = Missing pulse delay multiplier
Alt Pulse Term = Alternate Number of Pulses to terminate sampling