Rev c and earlier upgrade instructions – Rockwell Automation 2727 MobileView Machine Terminal and Guard Terminal Firmware Upgrade Kit User Manual
Page 2
2 MobileView Machine Terminal and Guard Terminal Firmware Upgrade Kit
Publication 2727-IN009A-EN-P - May 2004
4. Browse to the PC card and select the *.bin file. Click O.K. and then click the
“Start Update” button.
5. Select Yes to the next two warnings. After the progress bar completes, you
will be prompted to select O.K. to reboot the terminal. Select O.K.
Do not remove power from the unit until it boots into the new
Operating System.
6. After the unit reboots, a green progress bar will appear and the message
“erasing PSM, please wait…”. After the progress bar completes, the unit will
go blank for about 15 seconds and then boot into the new OS.
7. A touch screen calibration screen will also appear. The OS update is now
complete.
8. After performing the calibration, wait 5 to 10 minutes before doing a registry
back-up to save the new touch screen settings; the unit is still writing some
files at this point. After doing the registry back-up, you are now ready to
load ME Station.
Rev C and Earlier Upgrade Instructions
1. Copy all the files from the Upgrade folder on the CD
(Variant-Update-Tool.exe, KetopAPI.dll, softreset.exe, InstallCE_MOV~.exe,
and the *.bin file) to a PC card.
2. Back-up any files from folder Flash Storage that you want to keep to a PC
card or to a PC using Microsoft’s ActiveSync.
3. Browse to \windows\startup and delete file StartAPI.
4. Browse to the PC card and run softreset.exe.
5. After the unit resets, close the Terminal Server Client message box. Click on
Start and then Run command.
6. Browse to the PC card and select Variant-Update-Tool.exe. Then add a
space and /variant to the end of the executable. The Run command line
should look like this: “Storage Card\Variant-Update-Tool.exe” /variant. Hit
OK to execute the command.
IMPORTANT