Wiring to a 1797-tb3 or -tb3s terminal base unit – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual
Page 8
8 FLEX Ex NAMUR Input Module
Publication
1797-5.7 - March 2010
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit
Connect wiring to the 1797-TB3 or 1797-TB3S terminal base unit as shown
below.
1. Connect the individual input wiring to (+) terminals (0, 2, 4, 6, 8, 10,
12, 14) on the 0 to 15 row (A) and on the 16 to 33 row (B) (terminals
17, 19, 21, 23, 25, 27, 29, 31)as indicated in the table below.
2. Connect the associated input to the corresponding (-) terminal (1, 3,
5, 7, 9, 11, 13, 15) on the 0 to 15 row (A), and on the 16 to 33 row (B)
(terminals 18, 20, 22, 24, 26, 28, 30, 32) for each input as indicated in
the table below.
3. Connect +V dc power to terminal 34 on the 34 to 51 row (C).
4. Connect -V to terminal 35 on the 34 to 51 row (C).
WARNING
Make certain that you power this module with an intrinsically safe power
supply. Do not exceed the values listed in the specifications for this module.
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
41504
Row A
Row B
Row C
+
+
+
+
-
-
-
-
ch0
ch1
ch2
ch3
+V -V
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
No connections allowed to terminals 36 or 49.
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
+
-
+
-
+
-
+
-
ch7
ch6
ch5
ch4
+
-
+
-
+
-
+
-
+ -
+
-
+
-
+
-
ch8
ch9
ch10
ch11
ch15
ch14
ch13
ch12
+V
-V