4 FlexArmor 24V dc Sinking Input Modules

Publication 1798-IN001A-EN-P - January 2001

Install the Modules into the Baseplate

To install the modules into the Baseplate:

1. Hold the module at an angle and engage the top of the

module in the indention on the rear of the Baseplate.

2. Press the module down flush with the panel until the locking

lever locks.

3. Repeat these steps for each I/O module and each remaining

Baseplate I/O slot.

Screw down the module retaining screws to ensure IP67 compliance.

IMPORTANT

I/O modules can be installed in any slot location
to the right of the adapter module. The adapter is
capable of addressing up to eight I/O modules.

IMPORTANT

Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2
inch pounds).

Dust caps must have 4 inch pounds of torque
to maintain IP67 compliance.