Rockwell Automation 2193FZ Feeder Circuit Breaker Units Secure Support Pan and ChangeDoor Latch User Manual
Page 5

Rockwell Automation Publication 2100-IN092A-EN-P - April 2013
5
Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch
5. Disconnect the Feeder unit load wires and pull the load wires away from
the unit so the unit can be removed from the section.
6. Mark and disconnect control circuit wires if they interfere with the
removal of the Feeder unit.
7. Remove other cables or devices that prevent the unit from being
withdrawn.
8. Push the latch mechanism to the left with your right hand.
9. Pull the unit forward (outward) approximately 3 in. (7.62 cm) out of the
MCC.
Reposition your hands as necessary to properly support the unit while you
are removing the unit from the MCC.
10. Remove the unit from the MCC.
11. Carefully install protective caps or close manual shutters after the unit is
removed.
Automatic shutters close as units are removed.
12. If one of the following units is directly above or below the Feeder unit,
verify that the incoming power source is off and that the operator handle is
in the OFF/O position before you open that unit door:
• Main Lug Compartment unit (Bulletin 2191)
• Main Disconnect Switch unit (Bulletin 2192M)
• Main Circuit Breaker unit (Bulletin 2193M)
• Frame mounted unit
• Bottom horizontal wireway
ATTENTION: Plug-in MCC units can be heavy or awkward to handle. Use an
assistant or a platform lift device if necessary to help you handle the unit.
IMPORTANT
Units that are 1.0 space factor or larger have captive latches. Open the unit
door, disengage the captive latches at the front top and bottom of the unit, and
remove the unit from the section.
Latch Mechanism