5Ć2

indirectly by monitoringthe name with the VARIABLE

MONITOR function in the ReSource Software.
For both DCS 5000/AutoMax systems and AutoMate

systems, verify that the program reading the module is

executing fast enough to catch all of the input changes.

Step 5.

Verify that the hardware is workingcorrectly.
Toggle the input device. Verify that the LED associated

with the particular bit is also toggling. If it is not, the input

circuit on the module is malfunctioning.
Verify the hardware functionality by systematically

swappingout modules. If the problem is not corrected

after each swap, replace the original item before swapping

out the next item.
D To test local I/O, first replace the input module. Next,

replace the Processor module (s). If the problem

persists, take all of the modules out of the backplane

except one Processor module and the input module. If

the problem is now corrected, one of the other

modules in the rack is malfunctioning. Reconnect the

other modules one at a time until the problem

reappears. If none of these tests reveals the problem,

replace the backplane.

D To test remote I/O (DCS 5000/AutoMax systems only),

first verify that the remote I/O system is

communicatingwith the drop that contains the input

module beingtested. Next, determine whether the

input module is the only module that is not working. If

more than one module is not workingcorrectly, the

problem most likely lies in the remote I/O system.
To test the remote rack, first replace the input module.

Next, replace the slave remote I/O module. If the

problem persists, take all of the modules out of the

remote backplane except the slave remote I/O module

and the input module. If the problem is now corrected,

one of the other modules in the rack is malfunctioning.

Reconnect the other modules one at a time until the

problem reappears. If the problem proves to be

neither in the remote I/O system nor in the remote

rack, try replacingthe backplane.