No manual entry of special I/O configuration (SPIO CONFIG) information is
required. Module ID code automatically assigns the number of input and output
words required by the module. Refer to your configuration software documentation
for more information..
Set Up Channel 0
Determine the operating parameters for channel 0. The following example shows
the channel 0 configuration word defined with all defaults (0) except for the
channel enable (bit 11-1). The module is installed in slot 1. For details on channel
configuration, refer to the channel configuration worksheet on page 19.
TIP
For more detailed information on these procedures, refer to
Chapter 5 (Accessing Files to Configure I/O)of the user
manual.
TIP
For more detailed information on these procedures, refer to
Chapter 6 (Channel Configuration, Data and Status) of the
user manual.
O:1.1
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
Words 4, 6, & 7
(reserved)
Output Image
SLC 500 Controller
Data Files
Bit 15
Bit 0
Word 1
Word 2
Word 3
Address
O:1.0
Input Image
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Channel 0 Configuration Word
Word 0
Word 7
Input
Type
Data Format
Open Circuit
Temperature Units
Channel Enable
Unused
(8 words)
0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
Use Default Settings For:
Example Settings for Channel 0.
Set this bit (11) to enable channel. Address = O:1.0/11.
Type J Thermocouple
Engineering Units x 1
Data Word = 0 If Open Circuit
Degrees Celsius
O:1.2
O:1.3
O:1.7
Unused
Calibration Word 5