POINT I/O 4 Channel Analog Current Output Module 17

Publication

1734-IN034B-EN-P - November 2010

Specifications

Output Specifications

Attribute

Value

Number of outputs

4 analog, single-ended, non-isolated

Resolution current

16 bits - over 0…21mA
0.32

μ

A/cnt)

Output current terminal

0 mA output until communication established
4…20 mA user configurable
0…20 mA user configurable

Absolute accuracy

(1)

current

terminal, min

(1)

Includes offset, gain, non-linearity and repeatability error terms

0.4% (0.1% if calibrated)

Accuracy drift
w/temperature current
terminal

<50 ppm/°C

Resistive load on mA output

0…750

Ω

Conversion type

Digital to analog converter

Conversion rate

1

μ

s

Data format

Signed Integer

Calibration

Factory calibrated

Step response to 63% of FS

40

μ

s

Surge current

2 A for 10 ms, repeatable every 3 s

Status indicators

1 green/red network status indicator, logic side
1 green/red module status indicator, logic side
4 green/red output status indicators, logic side

IMPORTANT

Refer to Publication

1734-SG001

for information on breaking the field power

distribution bus. Refer to sections “When to Use the Field Power
Distributor” and “When to Use the Expansion Power Unit”.