POINT I/O 4 Channel Analog Current Output Module 13

Publication

1734-IN034B-EN-P - November 2010

Default Data Map for the 1734-OE4C Analog Output Module

Message size: 4 Bytes

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Produces
(scanner
Rx)

High Byte - Channel 1 Status

Low Byte - Channel 0 Status

Not used

H
C
A

L
C
A

C
M

C
F

Not used

H
C
A

L
C
A

C
M

C
F

High Byte - Channel 3 Status

Low Byte - Channel 2 Status

Not used

H
C
A

L
C
A

C
M

C
F

Not used

H
C
A

L
C
A

C
M

C
F

Where:

CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = Normal, 1 = calibration mode
LCA = Low Clamp Alarm; 0 = no error, 1 = fault
HCA = High Clamp Alarm; 0 = no error, 1 = fault

Message size: 8 bytes

15

14

13

12

11

10

09

08

0
7

0
6

0
5

0
4

0
3

0
2

0
1

0
0

Consumes
(scanner Tx)

Output Channel 0 High Byte

Output Channel 0 Low Byte

Output Channel 1 High Byte

Output Channel 1 Low Byte

Output Channel 2 High Byte

Output Channel 2 Low Byte

Output Channel 3 High Byte

Output Channel 3 Low Byte