EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal
ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Emissions
CISPR 11;
Group 1, Class A
Enclosure Type Rating
None (open-style)
Conductors Wire
Size
Category
14 AWG (2.5mm
2
) - 22 AWG (0.25mm
2
) solid or stranded
copper wire rated @ 75°C or greater
3/64 inch (1.2mm) insulation maximum
2
1
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
0 - Output 0 - NC
1 - Output 1 - NC
2 - Output 0 - NO
3 - Output 1 - NO
4 - Relay Common 0
5 - Relay Common 1
6 - +Supply
7 - +Supply
Mass
1.30 oz/36.9 grams
Agency Certification (when product
is marked)
C-
UL
-US
- UL Listed Industrial Control Equipment, certified
for US and Canada
C-
UL
-US
- UL Listed for Class I, Division 2, Groups A, B, C
and D Hazardous locations, certified for US and Canada
CE
2
-
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
2
- Australian Radiocommunications Act compliant
with AS/NZS 2064, Industrial Emissions
ODVA - ODVA Conformance tested to ODVA DeviceNet
specifications