Mounting expansion i/o, Minimum spacing – Rockwell Automation 1769-OF8C Compact Analog Output Module User Manual

Page 5

background image

Compact 1769-OF8C Analog Output Module 5

Publication 1769-IN065C-EN-P - June 2010

6. To allow communication between the controller and module, move the bus lever fully

to the left (4) until it clicks. Ensure it is locked firmly in place.

7. Attach an end cap terminator (5) to the last module in the system by using the

tongue-and-groove slots as before.

8. Lock the end cap bus terminator (6).

Mounting Expansion I/O

Minimum Spacing

Maintain spacing from
enclosure walls, wireways,
adjacent equipment, etc.
Allow 50 mm (2 in.) of space
on all sides for adequate
ventilation, as shown:

ATTENTION

When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper
electrical connection.

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the serial communication bus.

ATTENTION

During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into the
module. Debris that falls into the module could cause damage on
power up.

Top

Bottom

Side

Side

Host Controller

Compact I/

O

Compact I/

O

Compact I/

O

Compact I/

O

Compact I/

O

End Cap