Compact 1769-OF8C Analog Output Module 11

Publication 1769-IN065C-EN-P - June 2010

Removing the Finger-Safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining screws. The terminal
block will back away from the module as you remove the screws. When replacing the terminal
block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).

Wiring the Finger-Safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1. Loosen the terminal screws to be wired.

2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade

lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.

3. Tighten the terminal screw making sure the pressure plate secures the wire.

Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).

TIP

The terminal screws are non-captive. Therefore, it is possible to
use a ring lug [maximum 1/4 inch o.d. with a 0.139 inch
minimum i.d. (M3.5)] with the module.

TIP

If you need to remove the finger-safe cover, insert a screw
driver into one of the square, wiring holes and gently pry the
cover off. If you wire the terminal block with the finger-safe
cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way.

wiring the
finger-safe
terminal block

upper retaining screw

lower retaining screw