20 SLC 500™ RTD/Resistance Input Module
Publication 1746-IN012B-EN-P - May 2001
Input Specifications
RTD Types
platinum, nickel, nickel iron, copper
(For additional information on RTD types, see page 21.)
Temperature
Scale
(Selectable)
°C or °F and 0.1°C or 0.1°F
Resistance Scale
(Selectable)
1
Ω
or 0.1
Ω
for all resistance ranges; or 0.1
Ω
or 0.01
Ω
for 150
Ω
potentiometer.
Input Step
Response
Refer to the
SLC 500™ RTD/Resistance Input Module User Manual, 1746-6.7.
Channel Turn-On
Time
Requires up to one module update time
plus one of the following:
•
250 Hz Filter = 388 milliseconds
•
60 Hz Filter = 1,300 milliseconds
•
50 Hz Filter = 1,540 milliseconds
•
10 Hz Filter = 7,300 milliseconds
Channel Turn-Off
Time
Requires up to one module update time.
Reconfiguration
Time
Requires up to one module update time
plus one of the following:
•
250 Hz Filter = 124 milliseconds
•
60 Hz Filter = 504 milliseconds
•
50 Hz Filter = 604 milliseconds
•
10 Hz Filter = 3,004 milliseconds
RTD Excitation
Current
Two current values are user-selectable:
•
0.5 mA - Recommended for use with higher resistance ranges for both RTDs and
direct resistance inputs (1000
Ω
RTDs and 3000
Ω
resistance input). Refer to RTD
manufacturer for recommendations. Cannot use for 10
Ω
Copper RTD.
•
2.0 mA - Must use for 10
Ω
Copper RTD. Recommended to use for all other
RTD and direct resistance inputs, except 1000
Ω
RTDs and 3000
Ω
resistance
input ranges are limited. Refer to RTD manufacturer for recommendations.