16 SLC 500™ RTD/Resistance Input Module

Publication 1746-IN012B-EN-P - May 2001

Channel Configuration

Once the module is installed, each channel can be configured to establish the way
the channel will operate. You configure the channel by entering bit values into the
configuration word using your programming software. Channels 0 through 3 on the
NR4 are configured by entering bit values into output words 0 through 3
respectively. Output words 4 through 7 are used to further define the channel
configuration to allow you to choose a scaling format other than the module default
when using the proportional counts format. You can use words 4 and 5 to define
one user-set range. Use words 6 and 7 to define a second range. See the table
below for a bit-by-bit examination of the configuration word.

To Select

Make these bit settings

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

In

put

T

yp

e

100

Pt 385

0

0

0

0

200

Pt 385

0

0

0

1

500

Pt 385

0

0

1

0

1000

Pt 385

0

0

1

1

100

Pt 3916

0

1

0

0

200

Pt 3916

0

1

0

1

500

Pt 3916

0

1

1

0

1000

Pt 3916

0

1

1

1

10

Cu 426

(1)

1

0

0

0

120

Ni 618

(2)

1

0

0

1

120

Ni 672

1

0

1

0

604

NiFe 518

1

0

1

1

150

1

1

0

0

500

1

1

0

1

1000

1

1

1

0

3000

1

1

1

1

D

ata

F

orm

at

Engineering Units 1

(3)

0

0

Engineering Units
10

(4)

0

1

Scaled-for-PID

1

0

Raw/Proportional

1

1

Br

ok

en

In

pu

t

Set to Zero

0

0

Set to Upscale

0

1

Set to Downscale

1

0

Invalid

1

1

Te

mp

er

at

ur

e

Un

it

s

(5

)

°C

0

°F

1