Dip switch settings – Rockwell Automation 1747-ASB Remote I/O Adapter Module User Manual

Page 8

background image

8 Remote I/O Adapter Module

Publication 1747-IN014C-EN-P - January 2003

Dip Switch Settings

IMPORTANT

The ASB module can be configured as any logical rack number
from 0 to 77 octal. Rack numbers are determined by setting
switches SW1-1 through SW1-6, with ON equivalent to logical 0
and OFF equivalent to logical 1. Then, interpret this 6-bit binary
value as octal with SW1-6 as the least significant bit (LSB). For
example:

SW1-1

SW1-2

SW1-3

SW1-4

SW1-5

SW1-6

Rack

ON

OFF

ON

ON

ON

OFF

21 (octal)
17 (decimal)

(0)

(1)

(0)

(0)

(0)

(1)

1

O

N

24

5
6

7
8

3

SW1

Logical Rack Number Bit 5
(Most Significant Bit)

Logical Rack Number Bit 4

Logical Rack Number Bit 3

Logical Rack Number Bit 2

Logical Rack Number Bit 1

Logical Rack Number Bit 0 (LSB)

Logical Group Number Bit 1 (MSB)

Logical Group Number Bit 0
(Least Significant Bit)

Local Rack Number

ON = 0

OFF = 1

Local Group Number

7

8

Group

ON

ON

0 (default)

ON

OFF

2

OFF

ON

4

OFF

OFF

6