Adapter Status Indicator

Refer to the table for a description of the Adapter Status indicator.

Adapter Status Indicator

State

Status

Description

Recommended Action

Off

Off or
Process in
Progress

• No power supplied.
• Hardware check is in

progress.

• Initialization is in

progress.

Turn the adapter on or wait until the
hardware check or initialization has
finished.

Green

Operating
Normally

The adapter is operating
normally.

None.

Red

Hardware
Check

The adapter failed the
hardware check.

Check your hardware and cycle
power to the module. If that does not
fix the fault, contact your Rockwell
Automation representative. There is
the possibility that the module needs
to be replaced.