Troubleshoot with the indicators – Rockwell Automation 1738-XXXX ArmorPoint 24V dc Output Modules, Series A User Manual
Page 10
Publication 1738-IN001C-EN-E - June 2005
10 ArmorPoint 24V dc Output Modules, Series A
Troubleshoot with
the Indicators
Indication
Probable Cause
Module Status
Off
No power applied to device
Green
Device operating normally
Flashing Green
Device needs commissioning due to missing, incomplete, or
incorrect configuration
Flashing Red
Recoverable fault
Red
Unrecoverable fault - may require device replacement
Flashing Red/Green
Device is in self-test
Indication
Probable Cause
Network Status
Off
Device is not on line:
- Device has not completed dup_MAC-id test.
- Device not powered - check module status indicator.
Flashing Green
Device is on line but has no connections in the established state.
Green
Device is on line and has connections in the established state.
Flashing Red
One or more I/O connections in timed-out state.
Red
Critical link failure - failed communication device. Device detected
error that prevents it from communicating on the network.
Flashing Red/Green
Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request - long protocol message.
MOD
NET
0
1
2
3
4
5
6
7
1738-OB8EM12/A
24V dc Out
0
1
2
3
4
5
6
7
Module Status Indicator
43676
1738-OB8EM12
Network Status Indicator
I/O Status Indicators