Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual
Page 22
22 MicroLogix 1762-IF4 Analog Input Module
Publication 1762-IN012C-EN-P - June 2013
Environmental
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20... 65 °C (-4...149 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10... 500 Hz
Altitude, operating, max
2000 m (6562 ft)
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Panel mount - 50 g
DIN mount - 40 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
4 kV indirect
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±1 kV shielded line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz