General – Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual
Page 21

MicroLogix 1762-IF4 Analog Input Module 21
Publication 1762-IN012C-EN-P - June 2013
General
Attribute
Value
Dimensions, HxWxD
90 x 40.4 x 87 mm
(3.54 x 1.59 x 3.43 in.)
Approximate shipping weight (with carton)
235 g (8.28 oz)
Bus current draw, max
40 mA @ 5V DC
50 mA @ 24V DC
Analog normal operating range
Voltage: -10…10V DC
Current: 4…20 mA
Full scale
(1)
analog ranges
(1)
The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues
to convert the analog input up to the maximum full scale range.
Voltage: -10.5…10.5V DC
Current: -21…21 mA
Resolution
15 bits (bipolar)
Repeatability
(2)
(2)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
±0.12%
Input group to system isolation
30V AC/30V DC rated working voltage
(4)
(IEC Class 2 reinforced insulation)
type test: 500V AC or 707V DC for 1 min
(4)
Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth
ground.
Module power LED
On: indicates power is applied.
Recommended cable
Belden 8761 (shielded)
Vendor ID code
1
Product type code
10
Product code
67
Wire size
Wire Size and Terminal Screw Torque on page 15
Wiring category
(3)
(3)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
.
2 - on signal ports
Pilot duty rating
Not rated
Enclosure type rating
IP20
North American temp code
T3C