Rockwell Automation 1753-L28BBB-M_P GuardPLC 1600 Controllers User Manual
Page 19
19
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Environmental Specifications – GuardPLC 1600 Controllers
Attribute
1753-L28BBB-M, 1753-L28BBB-P
Temperature, nonoperating
• IEC 60068-2-1 (Test Ab, Unpackaged
nonoperating cold)
• IEC 60068-2-2 (Test Bb, Unpackaged nonoperating
dry heat)
• IEC 60068-2-14 (Test Na, Unpackaged
nonoperating thermal shock)
-40…85 °C (-40…185 °F)
Temperature, operating
• IEC 60068-2-1 (Test Ad, operating cold)
• IEC 60068-2-2 (Test Bd, operating dry heat)
• IEC 60068-2-14 (Test Nb, operating thermal
shock)
0…60 °C (32…140 °F)
Temperature, surrounding air
60 °C (140 °F)
Vibration
• IEC 60068-2-6 (Test Fc, operating)
1 g @ 10…150 Hz
Shock, operating
•
IEC 60068-2-27 (Test Ea, unpackaged shock)
15 g
Relative humidity
•
IEC 60068-2-30 (Test Db, unpackaged damp heat)
10…95% noncondensing
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
•
IEC 61000-4-2
•
6 kV contact discharges
•
8 kV air discharges
Radiated RF Immunity
•
IEC 61000-4-3
•
10V/m with 1kHz sine-wave 80% AM from 80
MHz…2000 MHz
•
1 V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B Immunity
•
IEC 61000-4-4
•
±2 kV @ 5 kHz on DC power ports
•
±1 kV @ 5 kHz on signal ports
•
±1 kV @ 5 kHz on communication ports
Surge Transient Immunity
•
IEC 61000-4-5
•
±500V line-line (DM) and ±500V line-earth (CM) on
DC power ports
•
±1 kV line-earth (CM) on signal ports
•
±1 kV line-earth (CM) on communication ports
Conducted RF Immunity
•
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150
kHz…80 MHz
Damped Oscillatory Wave Immunity
•
IEC 61000-4-12
•
±1 kV line-earth (CM) on signal ports
•
±1 kV line-earth (CM) on power ports