Rockwell Automation 1734-EPAC POINT I/O ac Power Supply User Manual
Page 14
![background image](/manuals/579789/14/background.png)
14 POINT I/O 120/240V ac Expansion Power Supply
Publication
1734-IN017A-EN-P - December 2005
POINTBus Output Current
Horizontal DIN rail mounting -
1.3 A at 5.2V dc
Vertical DIN rail mounting -
1.0 A at 5.2V dc
Input Overvoltage Protection MOV and fuse protected
Interruption
Output voltage will stay within specifications when input
drops out for 10 ms at 85V ac with max load.
Module Location
Between I/O modules in 1734 system
Breaks field power bus
Limitations
Use with POINT I/O adapters only
Power Consumption
15.1 W max @ 264V ac
Power Dissipation
8.4 W max @ 264V ac
Thermal Dissipation
28.7 BTU/hr max @ 264V ac
Isolation Voltage
264V continuous
Tested to withstand 3250V dc for 60 s
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
120…240V ac nom, 50…60 Hz
85…264V ac range
10 A max
Dimensions (HxWxL) Metric
Imperial
76.2 x 25.4 x 133.4 mm
3.00 x 1.00 x 5.25 in.
Environmental Conditions
Temperature, Operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
Temperature, Storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat):
5…95% noncondensing
Shock
Operating
Nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
50 g
Vibration
IEC 60068-2-6, (Test Fc, Operating)
5 g @ 10…500 Hz