TTL Input Module

9

Publication 1771ĆIN022B-EN-P - September 2002

Chassis Ground

SingleĆpoint Grounding

I/O chassis side plate

star washer

nut with captive washer

ground lug

1

ground lug

nut with captive washer

19480

When you connect grounding conductors to the I/O chassis grounding

stud, place a star washer under the first lug, then place a nut with captive

lock washer on top of each ground lug. Torque the nut with captive washer

to 18(+3) pound-inches.

grounding stud

1

Use the cup washer if crimpĆon lugs are not used.

#10 threadĆforming screw

externalĆtooth washers

19923

Use singleĆpoint grounding for extendedĆlocal I/O system

The systems must be grounded properly for proper

performance.

!

ATTENTION

!

6. You must connect both ends of the insulated signal return wire in

each transmission cable as follows:

connect one end to the dc common terminal of your +5V dc
Class 2 power supply

connect the other end to the dc common terminal of the field
wiring arm