Upgrade the 1770-kfc firmware – Rockwell Automation F1770-KFC(D)15 INSTL INSTR FLASH FIRMWARE KIT User Manual
Page 5
![background image](/manuals/579749/5/background.png)
Flash Firmware Kit
5
Publication 1770-5.9 - May 1998
Upgrade the 1770-KFC Firmware
Important: You cannot upgrade 1770-KFC firmware using
1770-KFCD binary files. Mixing binary files between
firmware can make the product inoperable.
To upgrade the 1770-KFC:
1.
Flash the main code by entering the following information at the
DOS prompt:
DLOAD KFC15.BIN COM1 38
•COM1 indicates which serial port you are using
•38 indicates a 38.4K baud rate
Change these settings, if necessary, based on your computer’s
serial port and baud rate.
You see this screen:
Look at the front of the module. The HOST LED blinks green,
the A LED blinks red, the B LED is off, and the STATUS LED is
solid green during the download.
When the download is complete, you see the following message:
Code Download into KFC Flash Memory Succeeded
If you see an error message, go to the troubleshooting section on
page 9.
2.
At the prompt, enter the following command:
DLOAD2 BOOT15.BIN COM1 38 0
Change the COM port and baud rate if necessary, based on your
computer’s serial port and baud rate.
KFC flash memory download utility - Version 0.8
Copyright 1994 by the Allen-Bradley Company
Succeeded Opening binary image file ‘KFC15.BIN’ to download
---------Downloading binary image to KFC flash memory