14 DeviceNet 1732 ArmorBlock I/O, Series A
DeviceNet 1732 ArmorBlock I/O Series A
General Specifications
Isolation
Type tested to 500V ac for 60 seconds between auxiliary power and network (I/O to logic)
Dimensions Inches (Millimeters)
1.9H x 2.7W x 6.9D (48H x 69W x 174D)
Indicators
Module Status - red/green
Network Status - red/green
Auxiliary Power - green
Point LED - yellow
Communication Rate
• 125Kbps @ 500 meters(1640 feet) for thick cable, flat media length 375 meters (1378 feet)
• 250Kbps @ 200 meters(600 feet) for thick cable, flat media length 150 meters (492 feet)
• 500Kbps @ 100 meters (330 feet) for thick cable, flat media length 75 meters (246 feet)
DeviceNet Power
Voltage
Maximum
Minimum
Current
Maximum
Minimum
25V dc
11V dc
100mA
100mA
Auxiliary Power - Voltage for I/O Channel Power
Maximum
Minimum
30V dc max
11V dc
Current for I/O Channel
-IB8, Maximum
-OB8E, Maximum
-8CFG, Maximum
450mA
4A
4A
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
-45 to 85°C (-49 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing
Shock
IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
Vibration
IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
Conductor Category
2
1, 2
See publication no. 889-CG001
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on signal ports
±2kV at 5kHz on communications ports
±4kV at 5.0kHz on power ports
Surge Transient Immunity
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±2kV line-earth(CM) on shielded
ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions
CSPR 11:
Group 1, Class A
Enclosure
Meets IP65/66/67 (when marked)