Rockwell Automation 1732D-XXXX DeviceNet ArmorBlock I/O, Series A User Manual
Page 12
Publication 1732D-IN001B-EN-E - May 2004
12 DeviceNet 1732 ArmorBlock I/O, Series A
The following table describes network status indicators.
The following table describes module status indicators.
Network Status Indicator - NS
Module’s State
Indicator
Status
Not Powered/
Not on line
Off
Device is not on-line:
• The device has not completed the
dup_MAC_id test yet.
• The device may not be powered yet.
On line, connected
Solid
Green
The device is operating in a normal condition and
the device is on line with connections in the
established state.
• As a Group 2 device, it means that the device
is allocated to a master.
On line, not connected
Flashing
Green
The device is on line with no connections in the
established state.
• The device has passed the dup_MAC_id
test, is on line, but has no established
connections to other nodes.
• As a Group 2 device, it means that the device
is not allocated to a master.
Critical link failure
Solid
Red
Failed communication device - The device has
detected an error that has rendered it incapable of
communication on the network (dup_MAC_id
failure or bus-off).
Connection time out
Flashing
Red
An I/O connection has timed out.
Module Status Indicator - MS
Module’s State
Indicator
Status
No Power
Off
There is no power applied to the module.
Device Operational
Green
The module is operating normally.
Module needs
commissioning
Flashing Green
The module needs commissioning due to
missing, incomplete or incorrect configuration.
Minor Fault
Flashing Red
Recoverable fault.
Critical Fault
Red
Watchdog timeout or the module has an
unrecoverable fault and may need replacing.