beautypg.com

Rockwell Automation 1732D-XXXX DeviceNet ArmorBlock I/O, Series A User Manual

Page 12

background image

Publication 1732D-IN001B-EN-E - May 2004

12 DeviceNet 1732 ArmorBlock I/O, Series A

The following table describes network status indicators.

The following table describes module status indicators.

Network Status Indicator - NS

Module’s State

Indicator

Status

Not Powered/

Not on line

Off

Device is not on-line:

• The device has not completed the

dup_MAC_id test yet.

• The device may not be powered yet.

On line, connected

Solid

Green

The device is operating in a normal condition and
the device is on line with connections in the
established state.

• As a Group 2 device, it means that the device

is allocated to a master.

On line, not connected

Flashing

Green

The device is on line with no connections in the
established state.

• The device has passed the dup_MAC_id

test, is on line, but has no established
connections to other nodes.

• As a Group 2 device, it means that the device

is not allocated to a master.

Critical link failure

Solid

Red

Failed communication device - The device has
detected an error that has rendered it incapable of
communication on the network (dup_MAC_id
failure or bus-off).

Connection time out

Flashing

Red

An I/O connection has timed out.

Module Status Indicator - MS

Module’s State

Indicator

Status

No Power

Off

There is no power applied to the module.

Device Operational

Green

The module is operating normally.

Module needs
commissioning

Flashing Green

The module needs commissioning due to
missing, incomplete or incorrect configuration.

Minor Fault

Flashing Red

Recoverable fault.

Critical Fault

Red

Watchdog timeout or the module has an
unrecoverable fault and may need replacing.