Rockwell Automation 1771-IBN DC (10-30V) INPUT Module Installation Instructions User Manual
Page 17

DC (10...30V) Input Module 17
Publication 1771-IN028D-EN-P - October 2008
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40…85 °C (-40…185 °F)
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
ESD immunity
IEC 61000-4-2:
4 kV indirect contact discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
1V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±1 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on
signal ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)