Rockwell Automation 1791DS-IB16 CompactBlock Guard I/O DeviceNet Safety Module User Manual
Page 11

CompactBlock Guard I/O DeviceNet Safety Modules 11
Publication
1791DS-IN002C-EN-P - April 2009
ATTENTION
Safety state of the module and its data is defined as the off state.
Serious injury can occur due to breakdown of safety outputs. Do not
connect loads beyond the rated value of the safety outputs.
Serious injury can occur due to loss of required safety functions. Wire
the module properly so that supply voltages or voltages for loads do
not touch the safety outputs accidentally or unintentionally.
As serious injury can occur due to loss of safety functions, use
appropriate devices as shown in the
Controlling Devices - Sample
Requirements
table.
Controlling Devices - Sample Requirements
Device
Requirement
Allen-Bradley Bulletin
Safety Components
Emergency
stop switch
Use approved devices with direct opening
mechanism complying with IEC/EN 60947-5-1.
Bulletin 800F, 800T
Door
interlocking
switch,
limit switch
Use approved devices with direct opening
mechanism complying with IEC/EN 60947-5-1
and capable of switching microloads of
24V DC 5 mA.
Bulletin 440K, 440G, or
440H for interlock
switch, Bulletin 440P or
802T for limit switch
Safety
sensor
Use approved devices complying with the
relevant product standards, regulations, and
rules in the country where used.
Any Allen-Bradley
Guardmaster product
Relay with
forcibly
guided
contacts
Use approved devices with forcibly guided
contacts complying with EN 50205. For
feedback purposes, use devices with contacts
capable of switching microloads of
24V DC 5 mA.
Bulletin 700S, 100S
Other
devices
Evaluate whether devices used are appropriate
to satisfy requirements of safety category
levels.