beautypg.com

Rockwell Automation 1794-IE8XOE4 FLEX I/O DC Input, Output, and Input/Output Analog Modules Installation User Manual

Page 16

background image

16 FLEX I/O DC Input, Output, and Input/Output Analog Modules

Publication 1794-IN106D-EN-E - January 2014

Environmental Specifications

Attribute

1794-IE12

1794-OE12

1794-IE8XOE4

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)

Temperature,

nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

EC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave

80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse

100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse

100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave

80% AM from 2000...2700 MHz

IEC 61000-4-3:
10V/m with 1 kHz sine-wave

80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse

100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse

100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave

80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV @ 5 kHz

on power ports

±4 kV @ 5 kHz

on shielded

signal ports

IEC 61000-4-4:

±4 kV @ 5 kHz

on power ports

±2 kV @ 5 kHz

on shielded

signal ports

IEC 61000-4-4:

±4 kV @ 5 kHz on power ports

±4 kV @ 5 kHz on shielded

signal ports

Conducted RF immunity IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz