background image

FLEX I/O ControlNet Redundant Media Adapter

5

Publication 1794-5.18 – September 1996

Comm A

Comm B

Status

Status Indicators

Probable Cause

Comm A and Comm B Simultaneously

Off

No power, or reset

Red

Adapter inoperative

Red/Grn – (flashing alternately)

Adapter self-test

Red/Off – (flashing alternately)

Bad node configuration (duplicate address)

Comm A or Comm B (individually)

Off

Channel disabled

Green

Channel operational

Flashing Grn/Off

Temporary network errors

Flashing Red/Off

Cable fault, broken cable, redundancy warning

Flashing Red/Grn

Bad network configuration

Status Indicator

Off

Channel disabled

Flashing Grn

On-line but not connected

Green

On-line, link okay, connected

Flashing Red

Recoverable fault

Red

Critical – adapter failure

1794-ACNR Specifications

I/O Capacity

8 modules