Dimensions Inches

(Millimeters)

3.00H x 2.36W x 5.25L

(76.2 Hx 60.0W x 133.4L)

Environmental Conditions

Operational Temperature

Storage Temperature

Relative Humidity

Shock

Operating

Non-operating

Vibration

-20 to +55

o

C (-4 to +131

o

F)

-40 to 85

o

C (-40 to 185

o

F)

5 to 95% noncondensing

30g peak acceleration, 11(±1)ms pulse width

50g peak acceleration, 11(±1)ms pulse width

Tested 5g @ 10-500Hz per IEC 68-2-6

Conductors Wire Size

Category

14 AWG (2.5mm

2

) - 22 AWG (0.25mm

2

) solid or

stranded max

3/64 inch (1.2mm) insulation max

2

1

Terminal Base Screw
Torque

5-7 pound-inches (0.5-0.6 Nm)

Field Wiring Terminations

DeviceNet

1 - Black Wire

-V

2 - Blue Wire

CAN Low

3 - Bare Wire

Drain

4 - White Wire

CAN High

5 - Red Wire

+V

Field Power Supply

0 - No Connection 1 - No Connection

2 - No Connection 3 - No Connection

4 - Common

5 - Common

6 - Supply

7 - Supply

Mass

12.02 oz/340.77 grams

Agency Certification
(when product is marked)

• C-UL Listed
• C-UL Class I, Division 2 Groups A, B, C and D

certified

• UL listed
• CE marked for all applicable directives
• C-Tick marked for all applicable acts

1

Use this conductor category information for planning conductor routing. Refer to publication
1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise Immunity.”