beautypg.com

Rockwell Automation 1734-ACNR Point I/O ControlNet Adapter Installation Instructions User Manual

Page 13

background image

13

Publication

1734-IN582B-EN-P - February 2005

Solid Red

Unrecoverable fault has occurred:

self test failure (checksum failure at powerup, ramtest failure at
powerup)

firmware fatal error

Flashing Green

Waiting for connection or ControlNet cable break

Solid Green

Module is operating correctly (normal mode)

ControlNet A/B Status

Viewed Together

Both Steady Off

Reset, no power or entire network interface deactivated

Alternating Red/Green

Self test mode

Alternating Red/Off

Bad/invalid node configuration (such as duplicate MAC ID)

Both Steady Red

Failed link interface

Viewed Individually

Steady Off

Channel disabled or channel not supported

Flashing Red/Green

Invalid link configuration

Flashing Red/Off

Severe Link error - link fault or no MAC frames received

Flashing Green/Off

Temporary channel error or listen-only

Steady Green

Normal operation - MAC frames are being received without
detected errors

PointBus Status

Off

Device not powered - check module status indicator

Alternating Red/Green

LED powerup test

Flashing Red

Recoverable fault has occurred:

• at power up the number of expected modules does not

equal the number of modules present

• a module is missing
• node fault (I/O connection timeout)