12 SLC 5/03, SLC 5/04, and SLC 5/05 Modular Processors

Publication 1747-IN009B-EN-P - March 2008

Troubleshooting Your SLC Processor

Before troubleshooting your SLC 500 system, please obtain an SLC 500 Modular
Hardware Style User Manual, publication 1747-UM011. Refer to the chapter on
troubleshooting.

In addition to the SLC 500 Modular Hardware Style User Manual, publication
1747-UM011, the SLC 500 Instruction Set Reference Manual, publication
1747-RM001, contains explanations and examples for the entire instruction set as
well as for all status words and bits. It also contains explanations for all possible
fault codes found in status word S:6.

Specifications

SLC 5/03, SLC 5/04, and SLC 5/05 Processors

Attribute

SLC 5/03

SLC 5/04

SLC 5/05

L531

L532

L533

L541

L542

L543

L551

L552

L553

Memory (words) 8 K

16 K

32 K

16 K

32 K

64 K

16 K

32 K

64 K

I/O capacity,
max

4096 discrete inputs/4096 discrete outputs

Local system,
max

3 chassis / 30 slots

Programming
instructions

107

Typical scan
time

(1)

(1)

The scan times are typical for a 1 K ladder logic program consisting of simple ladder logic and communication servicing.
Actual scan times depend on your program size, instructions used, and the communication protocol.

1 ms/K

0.9 ms/K

Bit execution
(XIC)

0.44 µs

0.37 µs

Programming
software

SLC 5/03s and SLC 5/04s: RSLogix 500,
SLC 5/05s: RSLogix 500