beautypg.com

Alternate mode (one channel at a time) input file – Rockwell Automation 1769-ASCII Compact Module User Manual

Page 17

background image

Compact 1769-ASCII Module 17

Publication

1769-IN068B-EN-P - May 2005

• CNO = Channel number of the output data being sent. This bit is set

by the PLC controller or other user program to tell the ASCII module
which port’s data is being sent to the ASCII module.

• Reserved bits should be set to 0.

Alternate Mode (One Channel at a Time) Input File

Maximum size is shown below. Refer to the Compact I/O 1769-ASCII
Module User Manual, publication 1769-UM012, to use smaller input files.

• Tx = Transmit
• Rx = Receive
• TS = Transmit sent. Indicates the ASCII module has sent the data

indicated by the Tx Transaction ID and can accept more transmit
data.

• ND = New data. Only used for Handshake mode.
• HE = Handshake error. Only used for Handshake mode.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Tx ID 0 Acknowledged

Rx Transaction ID Ch0

1

15

14

13

12

11

10 TG0 TS0 ND

0

HE0 NR

0

RF0 TF0 PA0 RO0 TO0

2

Tx ID 1 Acknowledged

Rx Transaction ID Ch1

3

15

14

13

12

11

10 TG1 TS1 ND

1

HE1 NR

1

RF1 TF1 PA1 RO1 TO1

4

Reserved

CNI

5

Reserved

CNO

6

Firmware Revision, Major

Firmware Revision, Minor

7

Length (Number of Bytes)

8

Character 1

Character 0

9

Character 3

Character 2

Character …

Character …

106

Character 197

Character 196

107

Character 199

Character 198