beautypg.com

Connect the d-sub connector pins – Rockwell Automation 1769-ASCII Compact Module User Manual

Page 13

background image

Compact 1769-ASCII Module 13

Publication

1769-IN068B-EN-P - May 2005

Connect the D-sub Connector Pins

All pins are active at all times.

IMPORTANT

Pins unused for a particular physical network must not be
connected via the serial cable to any other device. In
particular, do not use cables 1747-CP3 and 1756-CP3.

Pin

RS-232

RS-422

RS-485

1

Do Not Connect

Transmit Data -

Transmit/Receive Data -

2

Receive Data

Do Not Connect

Do Not Connect

3

Transmit Data

Do Not Connect

Do Not Connect

4

Do Not Connect

Receive Data -

Do Not Connect

5

Common

Common

Common

6

Do Not Connect

Receive Data +

Do Not Connect

7

Request To Send

Request To Send

Request To Send

8

Clear To Send

Clear To Send

Clear To Send

9

Do Not Connect

Transmit Data +

Transmit/Receive Data +