beautypg.com

Mounting expansion i/o, Minimum spacing, Panel mounting – Rockwell Automation 1769-OW16 Compact 16-Point AC/DC Relay Output Module User Manual

Page 5

background image

Compact™ 16-Point AC/DC Relay Output Module 5

Publication 1769-IN062A-EN-P - December 2001

7. Attach an end cap terminator (5) to the last module in the system by using

the tongue-and-groove slots as before.

8. Lock the end cap bus terminator (6).

Mounting Expansion I/O

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow
50 mm (2 in.) of space on
all sides for adequate
ventilation, as shown:

Panel Mounting

Mount the module to a panel using two screws per module. Use M4 or #8 panhead
screws. Mounting screws are required on every module.

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be
used to terminate the end of the serial communication
bus.

ATTENTION

!

During panel or DIN rail mounting of all devices, be sure that
all debris (metal chips, wire strands, etc.) is kept from falling
into the module. Debris that falls into the module could cause
damage on power up.

Top

Side

Bottom

Side

Host Controller

Compact

I/

O

Compact

I/

O

Compact

I/

O

Compact

I/

O

Compact

I/

O

End Cap