Output specifications – Rockwell Automation 1769-OW16 Compact 16-Point AC/DC Relay Output Module User Manual
Page 15
Compact™ 16-Point AC/DC Relay Output Module 15
Publication 1769-IN062A-EN-P - December 2001
Output Specifications
Specification
1769-OW16
Voltage Category
AC/DC normally open relay
Operating Voltage Range
5 to 265V ac
5 to 125V dc
Number of Outputs
16
Bus Current Draw (max.)
205 mA at 5V dc line
180 mA at 24V dc line
Heat Dissipation
4.75 Total Watts
(The Watts per point, plus the minimum Watts, with all points
energized.)
Signal Delay (max.) – resistive load
turn-on = 10 ms
turn-off = 10 ms
Off-State Leakage (max.)
0 mA
On-State Current (min.)
10 mA at 5V dc
Continuous Current per Point (max.)
2.5A (Also see "Relay Contact Ratings" on page 16.)
Continuous Current per Common (max.)
10A
Continuous Current per Module (max.)
20A
Power Supply Distance Rating
8 (The module may not be more than 8 modules away from the
power supply.)
Output Point to Bus Isolation
Verified by one of the following dielectric tests: 1836V ac for 1
sec. or 2596V dc for 2 sec.
265V ac working voltage (IEC Class 2 reinforced insulation)
Isolated Groups
Group 1: outputs 0 to 7
Group 2: outputs 8 to 15
Output Group to Output Group Isolation
Verified by one of the following dielectric tests: 1836V ac for
2 sec. or 2596V dc for 2 sec.
265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code
1
Product Type Code
7
Product Code
85