ArmorBlock LP2 4 Sinking Input Module
Publication 1792D-5.27- January 1999
For more information on indications see the Product Data publication
1792-2.1.
Specifications
Red
Blink
Solid
Connection Timed Out
Failed Communication: A duplicate node address exists or
module is at the wrong baud rate.
I/O Status Indicators
Function
Module Status Indicator
Point Indicator
Condition
Inputs
Green
Green
None
Yellow
No valid input
Valid input
4 Input Module - Cat. No. 1792D-4B0LP
Sinking Input Specifications
Max
Min
Inputs per block
4 - 3 wire or dry contact PNP devices
Sensor Source Current (per input)
50mA
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5Vdc
Off-state Current
1.5mA
General Specifications
Indicators
Network Status - red/green
Module Status - red/green
Point LED- yellow
Communication Rate
• 125Kbps @ 500 meters(1600 feet) for thick
cable, flat media length 375 meters (1230 feet)
• 250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters (246 feet)
DeviceNet Power Voltage
Current
25V dc
125mA (no sensors)
300mA (full load)
11V dc
Dimensions (assembled to base)
inches - (millimeters)
1.023H x 2.7w x 4.72D
(26)H x (68.5)W x (120)D