Communicate With Your ArmorBlock LP2 Module
This ArmorBlock module’s I/O is exchanged with the master through a
poll, change of state, or cyclic connection.
The module produces input data as follows:
Cyclic - allows configuration of the block as an I/O client. The block will
produce its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 4 input module scans the inputs producing a
response that reflects their status.
Change of state - productions occur when an input changes . If no input
change occurs within the expected packet rate, a heartbeat production
occurs. This heartbeat production tells the scanner module that the module
is alive and ready to communicate.
Refer to the table below for the word/bit definitions.
The DeviceNet Network uses advanced network technology, producer/
consumer communication, to increase network functionality and
throughput. Visit our web site at http://www.ab.com/networks for producer/
consumer technology information and updates.
Type of I/O Connections
Consumes
Produces
Cyclic
0 Byte
1 Byte
Polled
0 Byte
1 Byte
Change of State
0 Byte
1 Byte
Bit
07
06
05
04
03
02
01
00
Produces 0
RSVD
RSVD
RSVD
RSVD
I3
I2
I1
I0
Where: O I = Input RSVD = Reserved
Byte
Bit
Description
Produces 0
00-03
07
Input status bits: When the bit is set (1), the input is on. Bit
00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 =
input 3.
Reserved