Troubleshoot with the indicators, Interpret led indicators – Rockwell Automation 1738-IB4DM12 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics I.I. User Manual
Page 9
Publication 1738-IN021A-EN-E - January 2007
ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics 9
Troubleshoot With
the Indicators
Interpret LED Indicators
0
1
2
3
MOD
NET
1738-IB4DM12
24V dc In with
Diagnostics
0
1
2
3
IO Diagnostics:
Solid Red = Short
Flashing Red = Open
Module Status Indicators
43680
1738-IB4DM12
Network Status Indicators
I/O Status Indicators
Indication
Probable Cause
Recommended Action
Module Status
Off
No power applied to device
Apply power to device.
Green
Device operating normally
None.
Flashing Green
Device needs commissioning due to configuration
missing, incomplete or incorrect.
Configure device properly.
Flashing Red
Recoverable fault
1. Cycle power to device.
2. If condition persists, replace device.
Red
Unrecoverable fault - may require device
replacement
Replace device.
Flashing Red/Green
Device is in self-test
None.
Network Status
Off
Device is not on line:
- Device has not completed dup_MAC_ID test.
- Device not powered - check module status
indicator.
Apply power to device, wait for
dup_MAC_id to complete, and correct, as
needed.
Flashing Green
Device is on line but has no connections in the
established state.
None - device is in Idle or Program mode.
Green
Device is on line and has connections in the
established state.
None.
Flashing Red
One or more I/O connections in timed-out state.
Check for I/O module failure, and correct, as
needed.