Wire the module, Communicate with your module, Default data map - produced assembly instance 101 – Rockwell Automation 1738-IB4DM12 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics I.I. User Manual
Page 7
Publication 1738-IN021A-EN-E - January 2007
ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics 7
Wire the Module
Following are wiring instructions for the module.
1738-IB4DM12
Communicate With
Your Module
I/O messages are sent to (consumed) and received from (produced) the
module. These messages are mapped into the processor’s or scanner’s memory.
The module produces 1 or 2 bytes of input data (scanner Rx - status) based on
which produced assembly is selected. The default setup is 2 bytes.
Default Data Map - Produced Assembly Instance 101
ATTENTION
Make sure all connectors and caps are securely tightened to properly
seal the connections against leaks and maintain IP enclosure type
requirements.
To comply with the CE Low Voltage Directive (LVD), all connected I/O
must be powered from a source compliant with the following:
• Safety Extra Low Voltage (SELV) or Protected Extra Low
Voltage (PELV).
(view into connector)
Pin 1 - 24V dc (Sensor Source Voltage SSV)
Pin 2 - No Connect
Pin 3 - Common
Pin 4 - Input 0 (M12-A)
Input 1 (M12-B)
Input 2 (M12-C)
Input 3 (M12-D)
Pin 5 - No Connect
43664
Message Size: 2 Bytes
7
6
5
4
3
2
1
0
Produce 0 (Rx)
Fault
3
Fault
2
Fault
1
Fault
0
Input
3
Input
2
Input
1
Input
0
Produce 1 (Rx)
SC 3
SC 2
SC 1
SC 0
OW 3 OW 2 OW 1
OW 0
Consume (Tx)
No consumed data
Where: 0W = open wire, SC = short circuit, fault = open wire or short circuit.