POINT I/O Protected Sink Output Module 27
Publication
1734-IN585C-EN-E - December 2005
Surge Transient
Immunity
IEC 61000-4-5
+1 kV line-line (DM) and +2 kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Enclosure Type Rating
None (open-style)
Certification
Certification
Value
Certification
(1)
(when product is
marked)
c-UL-us UL
Listed
Industrial
Control Equipment, certified for
U.S. and Canada. See UL File E65584.
c-UL-us UL Listed for Class I, Division 2, Group A,B,C,D
Hazardous Locations, certified for U.S. and Canada.
See UL File E194810.
CE
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab.,Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers
(Clause 8, Zone A and B)
C-Tick Australian Radiocommunications Act,
compliant with:
AS/NZS CISPR11; Industrial Emissions
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.
POINT I/O and POINTBus are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Environmental Specifications