Mounting dimensions, Back cover – Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Communications Adapter User Manual
Page 5
Publication 1794-IN114C-EN-P - August 2010
5
PN-89164
Supersedes Publication 1794-IN114B-EN-P- April 2009
Copyright © 2010 Rockwell Automation, Inc. All rights reserved.
Mounting Dimensions
Specifications - Flex I/O PROFIBUS 1794-APBDPV1
Environmental Specifications
Certifications
Specification
Description
I/O capacity
8 modules
Input voltage rating
24V DC nom
19.2V...31.2 V DC (includes 5% AC ripple)
Input current
385 mA max, 309 mA at 24V DC
Inrush current
23 A for 2 ms
Communication rate
All rates up to 12.0 Mbits/s
Indicators
Status- red/green
PROFIBUS- red/green
Flexbus output current
640 mA max
Isolation voltage
50V (continuous), Basic Insulation Type
Profibus to FLEX backplane to power
Routine tested at 850V DC for 1 s, Profibus to Backplane to Power
Type tested at 850V AC for 60 s, Profibus to Backplane to Power
Power dissipation
4.2 W max @ 19.2V DC
Thermal dissipation
Max 14 BTU/hr @ 19.2V DC
Dimensions, approx.
(HxWxD)
87 x 69 x 69 mm
(3.4 x 2.7 x 2.7 in.)
Wire size
- Power
0.34... 2.5 mm
2
(22...12 AWG) solid or stranded copper wire rated at 75 °C
(167 °F ) or greater 1.2 mm (3/64 in.) insulation max
Wire category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
.
1 on power ports
2 on communications ports
North American temp code
T4
IEC temp code
T4
PROFIBUS cable
Standard drop cable
PROFIBUS connector plug
9-pin D-shell
Emclosure type rating
None (open-style)
(Inches)
Millimeters
(3.4)
87
(3.2)
80
(2.7)
68
(0.83)
21
(1.4)
35
A
(2.3)
59
B
(2.0)
50
(1.2)
28
C
44562
A = Mounting hole dimensions for optional mounting kit
B = DIN rail
C = Secure DIN rail approximately every 200mm (7.87 in.)
Module
1794-APBDPV1
Operating temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Storage temperature
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40…85 °C (–40…185 °F)
Surrounding air temperature, max.
55 °C (131 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30 g
Nonoperating 50 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2500 MHz
3V/m with 1 kHz sine-wave 80% AM from 2500…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5:
±2 kV line-earth (CM) on communications ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 10 kHz…80 MHz
Certifications
(when product is marked)
(1)
(1)
See the Product Certification link at
details.
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
II 3 G Ex nA II T4 X