Specifications

1794-IA8, 1794-IA8K

1794-IA8I

Number of Inputs

8, (1 group of 8), nonisolated

8 isolated

Module Location

Cat. No. 1794-TB2, -TB3, -TB3S and -TBN Terminal Base Units

On-state Voltage

65V ac minimum
120V ac nominal
132V ac maximum

On-state Current

1

7.1mA minimum

Off-state Voltage

43V ac maximum

Off-state Current

2.9mA minimum

Input Impedance

10.6K ohms nominal

Nominal Input Current

12mA @ 120V ac, 60Hz

Isolation Voltage

Tested at 2150V dc for 1s between
user and system
No isolation between individual
channels

Tested at 2150V dc for 1s between
user and system and between
individual channels

Input Filter Time

Refer to Input Filter Time table

Flexbus Current

30mA @5V dc

Power Dissipation

4.5W maximum @ 132V ac

Thermal Dissipation

Maximum 15.3 BTU/hr @ 132V ac

Specifications - Cat. No. 1794-IA16

Number of Inputs

16 (1 group of 16), nonisolated

Module Location

Cat. No. 1794-TB3, -TB3S and -TBN Terminal Base Units

On-state Voltage

74V ac minimum
120V ac nominal
132V ac maximum

On-state Current

1

minimum

nominal

maximum

5.49mA @ 74V ac, 47Hz

12.06mA @ 120V ac, 60Hz

14.81mA @ 132V ac, 63Hz

Off-state Voltage

20V ac maximum

Off-state Current

2.9mA minimum

Nominal Input Impedance

10K ohms

Nominal Input Current

12mA @ 120V ac, 60Hz

Isolation Voltage

Tested at 2150V dc for 1s between user and system
No isolation between individual channels

Flexbus Current

20mA

Power Dissipation

6.4W maximum @ 132V ac

Thermal Dissipation

Maximum 21.8 BTU/hr @ 132V ac

General Specifications

Input Filter Time

2

Off to On

On to Off

Refer to Input Filter Time chart for values.

Terminal Base Screw
Torque

7 pound-inches (0.8Nm)

9 pound-inches (1.0Nm) for 1794-TBN

Dimensions (with module
installed)

3.7H x 3.7W x 2.7D inches
94H x 94W x 69D mm

Indicators (field side
indication, customer
device driven)

1794-IA8, -IA8K - 8 yellow status indicators
1794-IA8I - 8 yellow status indicators
1794-IA16 - 16 yellow status indicators

External ac power
Supply voltage
Voltage range

120V ac nominal
1794-IA8, -IA8K, -IA8I - 85 to 132V ac, 47-63Hz
1794-IA16 - 74 to 132V ac, 47-63Hz

Keyswitch Position

8

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100% AM at 900Hz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

±2kV at 5kHz on power ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

3

12-22AWG (2.5mm

2

-0.34mm

2

) stranded copper wire rated at 75°C

or higher
3/64 inch (1.2mm) insulation maximum
2

Certifications (when
product is marked)

4

UL

UL Listed Industrial Control Equipment

CSA CSA certified for Class I, Division 2, Groups A, B, C and D

Hazardous locations

EEx

5

European Union 94/9/EEC ATEX Directive, compliant with:

EN 50021; Potentially Explosive Atmospheres,

Protection “n” (European Zone 2) - (1794-IA8K only)

CE

4

European Union 89/336/EEC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

European Union 73/23/EEC LVD Directive, compliant with:

EN 61131-2; Programmable Controllers

C-Tick

4

- Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

1

Ac inputs compatible with proximity switches with leakage ratings of I

leak

< 2.5mA and I

on

minimum = 5mA.

2

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter

time is time from the input signal dropping below the valid level to recognition by the module.

3

You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

4

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of

Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.