14 POINT I/O RS-232 and RS-485 ASCII Modules

Publication

1734-IN588B-EN-P - July 2003

Indication

Probable Cause

Network Status

Off

Device is not on-line

- Device has not completed dup_MAC_id test.

- Device not powered - check module status indicator

Flashing Green

Device is on-line but has no connections in the established state.

Green

Device on-line and has connections in the established state.

Flashing Red

One or more I/O connections in timed-out state

Red

Critical link failure - failed communication device. Device detected
error that prevents it communicating on the network.

Flashing

Red/Green

Communication faulted device - the device has detected a network
access error and is in communication faulted state. Device has
received and accepted an Identify Communication Faulted Request
- long protocol message.

Indication

Probable Cause

Transmit/Receive Status

Flashing Transmit/

Off Receive

Check wiring, ground, and RX connection. User parameter object to
view record numbers.

Flashing Receive/

Off Transmit

Check wiring. Watch TX light. If it does not flash, check that you
are properly initiating transmission. Use EDS parameter object to
try transmitting and watch the light. If it flashes, you are not
properly initiating transmission via I/O messaging. If it does flash,
check the remote device.

Off Transmit/

Green Receive

Check connections as you may have wired the device backwards.