26 POINT I/O 24V dc Digital Diagnostics Input Module

Publication

1734-IN029A-EN-E - January 2007

Surge Transient Immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal
ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from
150 kHz…80 MHz

Emissions

CISPR 11: Group 1, Class A

Enclosure Type Rating

None (open-style)

North American Temp Code

T5

Wire Size

0.25... 2.5 mm

2

(22...14 AWG) solid or stranded copper wire

rated at 75 °C (167 °F ) or greater
1.2 mm (3/64 in.) insulation max

Wire Category

1 - on signal ports

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications

Attribute