Rockwell Automation 1769-OF2 Compact (Series B or Later) Analog Output Module User Manual
Page 19

Compact™ 1769-OF2 (Series B or Later) Analog Output Module 19
Publication 1769-IN049A-EN-P
Specification
1769-OF2 (Series B or later)
Accuracy Drift with Temperature
Voltage Terminal: ±0.0086% FS per °C
Current Terminal: ±0.0058% FS per °C
Output Ripple
(1)
range 0 to 50 kHz
(referred to output range)
(1) Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
±0.05%
Non-linearity (in percent full scale) ±0.05%
Repeatability
(2)
(in percent full scale)
(2) Repeatability is the ability of the output module to reproduce output readings when the same controller
value is applied to it consecutively, under the same conditions and in the same direction.
±0.05%
Output Error Over Full Temperature
Range
(0 to 60°C [+32 to +140°F])
Voltage: ±0.8%
Current: ±0.55%
Output Offset Error
(0 to 60°C [+32 to +140°F])
±0.05%
Output Impedance
15
Ω
(typical)
Open and Short-Circuit Protection
Yes
Maximum Short-Circuit Current
21 mA
Output Overvoltage Protection
Yes
Time to Detect Open Wire
Condition (Current Mode)
10 ms typical
13.5 ms maximum
Output Response at System Power
Up and Power Down
± 0.5V dc spike for < 5 ms
Rated Working Voltage
(3)
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal,
including the input signal and the value that floats above ground potential (for example, 10V dc input signal
and 20V dc potential above ground).
30V ac/30V dc
Output Group to Bus Isolation
500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced
insulation)
Module OK LED
On: module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.
Channel Diagnostics
Over- or under-range by bit reporting
output wire broken or load resistance high by bit reporting
(current mode only)